  1. Pre-Operation Inspection: Perform routine tests including polarity verification, connection group check, insulation resistance measurement, and phase sequence confirmation before commissioning.
  2. Wiring Requirements: The primary winding must be connected in parallel with the circuit under test; the secondary winding must be connected in parallel with measuring instruments or protection devices, with correct polarity.
  3. Load Limitation: The secondary load must not exceed the transformer’s rated capacity to avoid increased measurement errors.
  4. Secondary Circuit Protection: The secondary winding must not be short-circuited. Install secondary fuses to prevent equipment damage from short-circuit currents.
  5. Safety Grounding: The secondary winding must be grounded at one point to prevent high voltage exposure to operators in the event of insulation failure.